sensor:
- platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${name} Ruecklauftemperatur an der Zirkulations Leitung"
id: ${name}_Ruecklauftemperatur_an_der_Zirkulations_Leitung
name: "${name} Drehzahl Netzpumpe"
id: ${name}_Drehzahl_Netzpumpe
register_type: read
address: 711
address: 700
unit_of_measurement: "%"
value_type: U_WORD
- platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${name} Netzrücklauf Temperatur"
id: ${name}_Netzrücklauf_Temperatur
register_type: read
address: 701
unit_of_measurement: "°C"
value_type: S_WORD
filters:
- multiply: 0.5
- platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${name} Strömungsschalter an der Brauchwasser Leitung"
id: ${name}_Stoemungsschalter_an_der_Brauchwasser_Leitung
register_type: read
address: 600
value_type: U_WORD
- platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${name} Drehzahl der Zirkulations Pumpe"
id: ${name}_Drehzahl_der_Zirkulations_Pumpe
register_type: read
address: 710
unit_of_measurement: "%"
value_type: U_WORD
binary_sensor:
- platform: template
name: "${name} Zirkulationspumpe AN AUS"
id: ${name}_Zirkulations_Pumpe_AN_AUS
name: "${name} Netzpumpe AN AUS"
id: ${name}_Netzpumpe_AN_AUS
lambda: |-
if (id(${name}_Drehzahl_der_Zirkulations_Pumpe).state > 0) {
if (id(${name}_Drehzahl_Netzpumpe).state > 0) {
return true;
} else {
return false;
}
number:
- platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${name} Bei welcher RL Temperatur an der Zirkulationsleitung soll die Pumpe ausschalten"
id: ${name}_Bei_welcher_RL_Temperatur_an_der_Zirkulationsleitung_soll_die_Pumpe_ausschalten
address: 600
unit_of_measurement: "°C"
value_type: S_WORD
multiply: 2
min_value: 20
max_value: 120