select:
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Betriebsart"
|
|
id: ${lower_name}_HK3_Betriebsart
|
|
address: 8048
|
|
value_type: U_WORD
|
|
optionsmap:
|
|
"Aus": 0
|
|
"Automatik": 1
|
|
"Extraheizen": 2
|
|
"Absenken": 3
|
|
"Dauerabsenken": 4
|
|
"Partybetrieb": 5
|
|
|
|
sensor:
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Vorlauf-Isttemperatur"
|
|
id: ${lower_name}_HK3_Vorlauf_Isttemperatur
|
|
register_type: read
|
|
address: 1090 #Wrong ?
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
filters:
|
|
- multiply: 0.5
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Vorlauf-Solltemperatur"
|
|
id: ${lower_name}_HK3_Vorlauf_Solltemperatur
|
|
register_type: read
|
|
address: 1091 #Wrong ?
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
filters:
|
|
- multiply: 0.5
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Raumtemperatur"
|
|
id: ${lower_name}_HK3_Raumtemperatur
|
|
register_type: read
|
|
address: 1092 #Wrong ?
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
filters:
|
|
- multiply: 0.5
|
|
|
|
binary_sensor:
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Pumpe AN AUS"
|
|
id: ${lower_name}_HK3_Pumpe_AN_AUS
|
|
register_type: coil
|
|
address: 1090
|
|
|
|
number:
|
|
# not correct yet ?
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Gewünschte Vorlauf-temperatur bei +10°C Außentemperatur"
|
|
id: ${lower_name}_HK3_Vorlauf_Temperatur_10C_Aussentemperatur
|
|
address: 1091
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: 10
|
|
max_value: 110
|
|
|
|
# not correct yet ?
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Gewünschte Vorlauf-temperatur bei -10°C Außentemperatur"
|
|
id: ${lower_name}_HK3_Vorlauf_Temperatur_minus_10C_Aussentemperatur
|
|
address: 1092
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: 10
|
|
max_value: 110
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Absenkung der Vorlauftemperatur im Absenkbetrieb"
|
|
id: ${lower_name}_HK3_Absenkung_der_Vorlauftemperatur_im_Absenkbetrieb
|
|
address: 1093
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: 0
|
|
max_value: 70
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Heizkreispumpe ausschalten wenn Vorlauf Soll kleiner ist als"
|
|
id: ${lower_name}_HK3_Heizkreispumpe_ausschalten_wenn_Vorlauf_Soll_kleiner_ist_als
|
|
address: 1099
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: 10
|
|
max_value: 30
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Gewünschte Raumtemperatur während des Heizbetriebs"
|
|
id: ${lower_name}_HK3_Gewuenschte_Raumtemperatur_waehrend_des_Heizbetriebs
|
|
address: 1095
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: 10
|
|
max_value: 30
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Gewünschte Raumtemperatur während des Absenkbetriebes"
|
|
id: ${lower_name}_HK3_Gewuenschte_Raumtemperatur_waehrend_des_Absenkbetriebes
|
|
address: 1100
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: 10
|
|
max_value: 30
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Außentemperatur, unter der die Heizkreispumpe im Heizbetrieb einschaltet"
|
|
id: ${lower_name}_HK3_Aussentemperatur_unter_der_die_Heizkreispumpe_im_Heizbetrieb_einschaltet
|
|
address: 1096
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: -20
|
|
max_value: 50
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Außentemperatur, unter der die Heizkreispumpe im Absenkbetrieb einschaltet"
|
|
id: ${lower_name}_HK3_Aussentemperatur_unter_der_die_Heizkreispumpe_im_Absenkbetrieb_einschaltet
|
|
address: 1097
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: -20
|
|
max_value: 50
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Frostschutztemperatur"
|
|
id: ${lower_name}_HK3_Frostschutztemperatur
|
|
address: 1098
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
multiply: 2
|
|
min_value: -10
|
|
max_value: 20
|
|
|
|
- platform: modbus_controller
|
|
modbus_controller_id: ${modbus_controller_id}
|
|
name: "${hk3_name} - Temp. am Puffer oben ab der der Überhitzungsschutz aktiv wird"
|
|
id: ${lower_name}_HK3_Temp_am_Puffer_oben_ab_der_der_Ueberhitzungsschutz_aktiv_wird
|
|
address: 1105
|
|
unit_of_measurement: "°C"
|
|
value_type: S_WORD
|
|
min_value: 60
|
|
max_value: 120
|