@@ -0,0 +1,169 @@
|
||||
select:
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Betriebsart"
|
||||
id: ${name}_HK3_Betriebsart
|
||||
address: 8048
|
||||
value_type: U_WORD
|
||||
optionsmap:
|
||||
"Aus": 0
|
||||
"Automatik": 1
|
||||
"Extraheizen": 2
|
||||
"Absenken": 3
|
||||
"Dauerabsenken": 4
|
||||
"Partybetrieb": 5
|
||||
|
||||
sensor:
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Vorlauf-Isttemperatur"
|
||||
id: ${name}_HK3_Vorlauf_Isttemperatur
|
||||
register_type: read
|
||||
address: 1090 #Wrong ?
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
filters:
|
||||
- multiply: 0.5
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Vorlauf-Solltemperatur"
|
||||
id: ${name}_HK3_Vorlauf_Solltemperatur
|
||||
register_type: read
|
||||
address: 1091 #Wrong ?
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
filters:
|
||||
- multiply: 0.5
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Raumtemperatur"
|
||||
id: ${name}_HK3_Raumtemperatur
|
||||
register_type: read
|
||||
address: 1092 #Wrong ?
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
filters:
|
||||
- multiply: 0.5
|
||||
|
||||
binary_sensor:
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Pumpe AN AUS"
|
||||
id: ${name}_HK3_Pumpe_AN_AUS
|
||||
register_type: coil
|
||||
|
||||
address: 1089
|
||||
|
||||
number:
|
||||
# not correct yet ?
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Gewünschte Vorlauf-temperatur bei +10°C Außentemperatur"
|
||||
id: ${name}_HK3_Vorlauf_Temperatur_10C_Aussentemperatur
|
||||
address: 1091
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: 10
|
||||
max_value: 110
|
||||
|
||||
# not correct yet ?
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Gewünschte Vorlauf-temperatur bei -10°C Außentemperatur"
|
||||
id: ${name}_HK3_Vorlauf_Temperatur_minus_10C_Aussentemperatur
|
||||
address: 1092
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: 10
|
||||
max_value: 110
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Absenkung der Vorlauftemperatur im Absenkbetrieb"
|
||||
id: ${name}_HK3_Absenkung_der_Vorlauftemperatur_im_Absenkbetrieb
|
||||
address: 1093
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: 0
|
||||
max_value: 70
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Heizkreispumpe ausschalten wenn Vorlauf Soll kleiner ist als"
|
||||
id: ${name}_HK3_Heizkreispumpe_ausschalten_wenn_Vorlauf_Soll_kleiner_ist_als
|
||||
address: 1099
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: 10
|
||||
max_value: 30
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Gewünschte Raumtemperatur während des Heizbetriebs"
|
||||
id: ${name}_HK3_Gewuenschte_Raumtemperatur_während_des_Heizbetriebs
|
||||
address: 1095
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: 10
|
||||
max_value: 30
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Gewünschte Raumtemperatur während des Absenkbetriebes"
|
||||
id: ${name}_HK3_Gewuenschte_Raumtemperatur_während_des_Absenkbetriebes
|
||||
address: 1100
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: 10
|
||||
max_value: 30
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Außentemperatur, unter der die Heizkreispumpe im Heizbetrieb einschaltet"
|
||||
id: ${name}_HK3_Aussentemperatur_unter_der_die_Heizkreispumpe_im_Heizbetrieb_einschaltet
|
||||
address: 1096
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: -20
|
||||
max_value: 50
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Außentemperatur, unter der die Heizkreispumpe im Absenkbetrieb einschaltet"
|
||||
id: ${name}_HK3_Aussentemperatur_unter_der_die_Heizkreispumpe_im_Absenkbetrieb_einschaltet
|
||||
address: 1097
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: -20
|
||||
max_value: 50
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Frostschutztemperatur"
|
||||
id: ${name}_HK3_Frostschutztemperatur
|
||||
address: 1098
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
multiply: 2
|
||||
min_value: -10
|
||||
max_value: 20
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${hk3_name} - Temp. am Puffer oben ab der der Überhitzungsschutz aktiv wird"
|
||||
id: ${name}_HK3_Temp_am_Puffer_oben_ab_der_der_Ueberhitzungsschutz_aktiv_wird
|
||||
address: 1105
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
min_value: 60
|
||||
max_value: 120
|
||||