moved files to main directory
This commit is contained in:
1 parent
8ce8162385
commit
502138f166
7 files changed
No files matched your search
+135
@@ -0,0 +1,135 @@
|
||||
sensor:
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Kesseltemperatur"
|
||||
id: ${name}_Kesseltemperatur
|
||||
register_type: read
|
||||
address: 0
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
filters:
|
||||
- multiply: 0.5
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Abgastemperatur"
|
||||
id: ${name}_Abgastemperatur
|
||||
register_type: read
|
||||
address: 1
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Verbleibende Heizstunden bis zur Asche entleeren Warnung"
|
||||
id: ${name}_Verbleibende_Heizstunden_bis_zur_Asche_entleeren_Warnung
|
||||
register_type: read
|
||||
address: 86
|
||||
unit_of_measurement: "h"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Saugzug - Ansteuerung"
|
||||
id: ${name}_Saugzug_Ansteuerung
|
||||
register_type: read
|
||||
address: 12
|
||||
unit_of_measurement: "%"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Saugzugdrehzahl"
|
||||
id: ${name}_Saugzugdrehzahl
|
||||
register_type: read
|
||||
address: 6
|
||||
unit_of_measurement: "rpm"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Sauerstoffregler"
|
||||
id: ${name}_Sauerstoffregler
|
||||
register_type: read
|
||||
address: 16
|
||||
unit_of_measurement: "%"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Restsauerstoffgehalt"
|
||||
id: ${name}_Restsauerstoffgehalt
|
||||
register_type: read
|
||||
address: 3
|
||||
unit_of_measurement: "%"
|
||||
accuracy_decimals: 1
|
||||
value_type: U_WORD
|
||||
filters:
|
||||
- multiply: 0.1
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Rücklauffühler"
|
||||
id: ${name}_Ruecklauffuehler
|
||||
register_type: read
|
||||
address: 9
|
||||
unit_of_measurement: "°C"
|
||||
value_type: U_WORD
|
||||
filters:
|
||||
- multiply: 0.5
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Primärluft"
|
||||
id: ${name}_Primaerluft
|
||||
register_type: read
|
||||
address: 11
|
||||
unit_of_measurement: "%"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Sekundärluft"
|
||||
id: ${name}_Sekundaerluft
|
||||
register_type: read
|
||||
address: 13
|
||||
unit_of_measurement: "%"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Betriebsstunden"
|
||||
id: ${name}_Betriebsstunden
|
||||
register_type: read
|
||||
address: 20
|
||||
unit_of_measurement: "h"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Stunden seit letzter Wartung"
|
||||
id: ${name}_Stunden_seit_letzter_Wartung
|
||||
register_type: read
|
||||
address: 55
|
||||
unit_of_measurement: "h"
|
||||
value_type: U_WORD
|
||||
|
||||
- platform: modbus_controller
|
||||
modbus_controller_id: ${modbus_controller_id}
|
||||
name: "${name} Betriebsstunden in der Feuererhaltung"
|
||||
id: ${name}_Betriebsstunden_in_der_Feuererhaltung
|
||||
register_type: read
|
||||
address: 24
|
||||
unit_of_measurement: "h"
|
||||
value_type: U_WORD
|
||||
|
||||
binary_sensor:
|
||||
- platform: template
|
||||
name: "${name} Kesselzustand Heizen"
|
||||
id: ${name}_Kesselzustand_Heizen
|
||||
lambda: |-
|
||||
if (id(${name}_Kesselzustand).state == "Heizen") {
|
||||
return true;
|
||||
} else {
|
||||
return false;
|
||||
}
|
||||
Reference in new issue
Block a user